Product Features
- The solid-insulation-embedded pole vacuum interrupter is used to realize maintenance-free of products;
 - The level of salt spray resistance test is up to 300 hrs;
 - Use the German INA customized copper-based high-pressure alloy oil-free bearings;
 - The passivation surface treatment process of zinc-cobalt alloy hexavalent chromium in Malaysia is introduced;
 - The design of mechanism is optimized, with comprehensive strength and rigidity at leading level;
 - Mechanical life of 30,000 cycles;
 - The spring mechanism is self-contained with energy-storage lever, both convenient and expedient.
 

Structural Characteristics
Overview
- The main circuits of ZN139-12/G-type vacuum circuit breakers are in form of solid-insulation-embedded pole. The operating mechanisms are divided into two types: spring-operated type and permanent magnet type.
 - The ZN139-12 / G-type vacuum circuit breaker products can be used separately, or used in the mid-set switchgear and fixed switchgear.
 
Insulation Form
- The ZN139-12/G vacuum circuit breaker is in overall structure of front-and-rear arrangement of the actuator and the primary conductive circuit. The main electrical circuit part is in three-phase floor-type structure.
 
Main Specifications and Technical Parameters
Main Specifications and Technical Parameters of Circuit Breaker
| No. | Description | Unit | Parameters | ||
|---|---|---|---|---|---|
| 1 | Rated voltage | kV | 12 | ||
| 2 | Rated power frequency withstand voltage (1 min) | kV | 42/48 | ||
| 3 | Rated lightning impulse/fracture withstand voltage (peak) | kV | 75/85 | ||
| 4 | Rated frequency | Hz | 50 | ||
| 5 | Rated current | A | 630 1250  | 
                                    630、1250 1600、2000、2500  | 
                                    1250、1600、2000 2500、3150、4000*  | 
                                
| 6 | Rated short-circuit breaking current | kA | 20 25 | 31.5 | 40 | 
| 7 | Rated short-circuit making current | kA | 50 63 | 80 | 100 | 
| 8 | Rated peak withstand current | kA | 50 63 | 80 | 100 | 
| 9 | Rated thermal stability current (effective value) | kA | 20 25 | 31.5 | 40 | 
| 10 | Rated short-circuit duration | s | 4 | ||
| 11 | Rated operations of short-circuit breaking current | Number of cycles | 30 | 30 | 20 | 
| 12 | Mechanical life | Number of cycles | 30000 | ||
| 13 | Rated single/back to back capacitor bank breaking current | A | 630/400(40kA for 800/400) | ||
| 14 | Phase-to-phase spacing | mm | below 1600A:210±1.5 above 2000A:275±1.5  | 
                                ||
| 15 | Contacts spacing | mm | 9±1 | ||
| 16 | Contact overtravel | mm | 3±0.5 | ||
| 17 | Allowable wearing accumulation thickness of dynamic and static contacts | mm | 3 | ||
| 18 | Time interval between opening of first and last phase of three phase circuit-breaker | ms | ≤ 2 | ||
| 19 | Bouncing time of contactor closed | ms | ≤ 2 (40kA ≤ 3) | ||
| 20 | Opening time | ms | 20-55 | ||
| 21 | Closing time | ms | 35-70 | ||
| 22 | Rated operating sequence | 0.3s   180s 0——CO——CO  | 
                                    180s   180s 0——CO——CO  | 
                                ||
| 23 | Mechanical system c | ||||